Diesel generator technical data

Model Operating mode Power speed
FKS-C1000   kW KVA rpm
Prime power 1000 1250 1500
Standby power 1100 1375

-. Diesel engine performance meets GB/T2820

-. The calibrated power is based on GB/T1147.1

→Prime power: For variable load applications, there is no limit on operating hours throughout the year. The average allowable output power for 24 hours of continuous operation shall not exceed 80% of the usual rated power.

→ Standby power: It is applied when the grid power is out of power, or applied under test conditions, and the annual use time does not exceed 200 hours at most. The average allowable output power for 24 hours of continuous operation shall not exceed 80% of the standby rated power.

Item

parameter

Unit Type

FKS-C1000

Main and standby power (KW)

1000/1100

Rated voltage (V)

400

Rated current (A)

1800

Rated frequency (Hz)

50

Rated speed r/min

1500

Speed control system

Electronic speed control

Short circuit protection

air switch

Power factor

0.8

No-load voltage waveform distortion (≤%)

3%

Steady state voltage deviation (≤%)

0.5%

Transient voltage deviation (≤%)

+20% ~ -15%

Voltage stabilization time (s)

1.0S

Voltage modulation (≤%)

0.25%

Frequency drop (≤%)

3%

Transient frequency deviation (≤%)

+10% ~ -7%

Frequency recovery time (s)

1S

Steady-state frequency band (≤%)

0.25%

Standard atmospheric conditions

GB1105ISO3046

Atmospheric pressure

100Kpa400m

Environment temperature (℃)

40

Relative humidity(%)

80

Noise dB (A) LP7M

105

 

Unit size (length*width*height) (mm)

4900*2028*2425