Diesel generator technical data
Model | Operating mode | Power | speed | |
FKS-C1000 | kW | KVA | rpm | |
Prime power | 1000 | 1250 | 1500 | |
Standby power | 1100 | 1375 |
-. Diesel engine performance meets GB/T2820
-. The calibrated power is based on GB/T1147.1
→Prime power: For variable load applications, there is no limit on operating hours throughout the year. The average allowable output power for 24 hours of continuous operation shall not exceed 80% of the usual rated power.
→ Standby power: It is applied when the grid power is out of power, or applied under test conditions, and the annual use time does not exceed 200 hours at most. The average allowable output power for 24 hours of continuous operation shall not exceed 80% of the standby rated power.
Item |
parameter |
Unit Type |
FKS-C1000 |
Main and standby power (KW) |
1000/1100 |
Rated voltage (V) |
400 |
Rated current (A) |
1800 |
Rated frequency (Hz) |
50 |
Rated speed r/min |
1500 |
Speed control system |
Electronic speed control |
Short circuit protection |
air switch |
Power factor |
0.8 |
No-load voltage waveform distortion (≤%) |
3% |
Steady state voltage deviation (≤%) |
0.5% |
Transient voltage deviation (≤%) |
+20% ~ -15% |
Voltage stabilization time (s) |
1.0S |
Voltage modulation (≤%) |
0.25% |
Frequency drop (≤%) |
3% |
Transient frequency deviation (≤%) |
+10% ~ -7% |
Frequency recovery time (s) |
1S |
Steady-state frequency band (≤%) |
0.25% |
Standard atmospheric conditions |
GB1105,ISO3046 |
Atmospheric pressure |
100Kpa(400m) |
Environment temperature (℃) |
40 |
Relative humidity(%) |
80 |
Noise dB (A) LP7M |
105 |
|
Unit size (length*width*height) (mm) 4900*2028*2425 |